.Buildings.Examples.VAVReheat.Validation.BaseClasses.Floor

Information

This model is used in the model Buildings.Examples.VAVReheat.Validation.TraceSubstance. It extends Buildings.Examples.VAVReheat.BaseClasses.Floor with CO2 generation from people and CO2 from outside air infiltration. Calculation of the generation from people uses the internal gain schedule and uses 0.05 people per m2 along with the zone area to calculate the number of people. Then, it assumes CO2 generation is 0.0048 l/s per person (Table 5, Persily and De Jonge 2017) and density of CO2 to be 1.8 kg/m3, making CO2 generation equal to 8.64e-6 kg/s per person. Outside air CO2 concentration is assumed 400 ppm.

References

Persily, A. and De Jonge, L. (2017). Carbon dioxide generation rates for building occupants. Indoor Air, 27, 868–879. https://doi.org/10.1111/ina.12383.

Revisions


Generated at 2024-10-24T18:25:30Z by OpenModelicaOpenModelica 1.24.0 using GenerateDoc.mos