modelWetFluid
Organic Rankine cycle with a wet working fluid
Extends from Buildings.Fluid.CHPs.OrganicRankine.BaseClasses.Validation.DryFluid (Organic Rankine cycle with a dry working fluid).
Information
This model is largely the same as Buildings.Fluid.CHPs.OrganicRankine.BaseClasses.Validation.DryFluid, except that it validates the handling of wet working fluids. As a result, a superheating temperature is computed that ensures the expansion does not land under the dome. How this superheating temperature is found is explained in the documentation of Buildings.Fluid.CHPs.OrganicRankine.ConstantEvaporation.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.ThermodynamicTemperature | TEva (from DryFluid) | 450 | Evaporating temperature |
| Modelica.Units.SI.ThermodynamicTemperature | TCon (from DryFluid) | 310 | Condensing temperature |
| Modelica.Units.SI.Efficiency | etaExp (from DryFluid) | 0.85 | Expander efficiency |
| Modelica.Units.SI.Efficiency | etaPum (from DryFluid) | 0.7 | Pump efficiency |
| Buildings.Fluid.CHPs.OrganicRankine.Data.WorkingFluids.Toluene | pro (from DryFluid) |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Fluid.CHPs.OrganicRankine.BaseClasses.InterpolateStates | cyc (from DryFluid) | Interpolate working fluid states in the cycle |
Revisions
-
March 04, 2023, by Hongxiang Fu:
First implementation. This is for #3433.