Model for an indirect steam heated absorption chiller based on
performance curves. The model uses performance curves similar to
the EnergyPlus model Chiller:Absorption:Indirect.
The model uses six functions to predict the chiller cooling
capacity, power consumption for the chiller pump and the generator
heat flow rate and the condenser heat flow. These functions use the
performance data stored in the record per. The
computations are as follows:
The capacity function of the evaporator is
capFuneva = A1 + A2 Teva,lvg + A3 T2eva,lvg + A4 T3eva,lvg.
The capacity function of the condenser is
capFuncon = B1 + B2 Tcon,ent + B3 T2con,ent + B4 T3con,ent.
These capacity functions are used to compute the available cooling capacity of the evaporator as
Q̇eva,ava = capFuneva capFuncon Q̇eva,0,
where Q̇eva,0 is obtained from the performance
data per.QEva_flow_nominal. Let
Q̇eva,set denote the heat required to meet the
set point TSet. Then, the model computes the part load
ratio as
PLR =min(Q̇eva,set/Q̇eva,ava, PLRmax).
Hence, the model ensures that the chiller capacity does not
exceed the chiller capacity specified by the parameter
per.PLRMax. The cycling ratio is computed as
CR = min(PLR/PLRmin, 1.0),
where PRLmin is obtained from the performance
record per.PLRMin. This ratio expresses the fraction
of time that a chiller would run if it were to cycle because its
load is smaller than the minimal load at which it can operate. Note
that this model continuously operates even if the part load ratio
is below the minimum part load ratio. Its leaving evaporator and
condenser temperature can therefore be considered as an average
temperature between the modes when the compressor is off and
on.
Using the part load ratio, the energy input ratio of the chiller pump is
EIRP = C1 + C2PLR+C3PLR2.
The generator heat input ratio is
genHIR = D1 + D2PLR+D3PLR2+D4PLR3.
Two additional curves modify the heat input requirement based on the condenser inlet water temperature and the evaporator outlet water temperature. Specifically, the generator heat modifier based on the condenser inlet water temperature is
genTcon = E1 + E2 Tcon,ent + E3 T2con,ent + E4 T3con,ent,
and the generator heat modifier based on the evaporator inlet water temperature is
genTeva= F1 + F2 Teva,lvg + F3 T2eva,lvg + F4 T3eva,lvg.
The main outputs of the model that are to be used in energy
analysis are the required generator heat QGen_flow and
the electric power consumption of the chiller pump P.
For example, if the chiller were to be regenerated with steam, then
QGen_flow is the heat that must be provided by a steam
loop. This model computes the required generator heat as
Q̇gen = -Q̇eva,ava genHIR genTcon genTeva CR.
The pump power consumption is
P = EIRP CR P0,
where P0 is the pump nominal power obtained
from the performance data per.P_nominal. The heat
balance of the chiller is
Q̇con = -Q̇eva + Q̇gen + P.
The equipment performance data is obtained from the record
per, which is an instance of Buildings.Fluid.Chillers.Data.AbsorptionIndirectSteam.
Additional performance curves can be developed using two available
techniques (Hydeman and Gillespie, 2002). The first technique is
called the Least-squares Linear Regression method and is used when
sufficient performance data exist to employ standard least-square
linear regression techniques. The second technique is called
Reference Curve Method and is used when insufficient performance
data exist to apply linear regression techniques. A detailed
description of both techniques can be found in Hydeman and
Gillespie (2002).