Base class for model of an electric chiller, based on the DOE-2.1 chiller model and the
CoolTools chiller model that are implemented in EnergyPlus as the models
Chiller:Electric:EIR
and Chiller:Electric:ReformulatedEIR
.
The model takes as an input the set point for the leaving chilled water temperature, which is met if the chiller has sufficient capacity. Thus, the model has a built-in, ideal temperature control. The model has three tests on the part load ratio and the cycling ratio:
PLR1 =min(QEva_flow_set/QEva_flow_ava, PLRMax)ensures that the chiller capacity does not exceed the chiller capacity specified by the parameter
PLRMax
.
CR = min(PLR1/per.PRLMin, 1.0)computes a cycling ratio. This ratio expresses the fraction of time that a chiller would run if it were to cycle because its load is smaller than the minimal load at which it can operature. Notice that this model does continuously operature even if the part load ratio is below the minimum part load ratio. Its leaving evaporator and condenser temperature can therefore be considered as an average temperature between the modes where the compressor is off and on.
PLR2 = max(PLRMinUnl, PLR1)computes the part load ratio of the compressor. The assumption is that for a part load ratio below
PLRMinUnl
,
the chiller uses hot gas bypass to reduce the capacity, while the compressor
power draw does not change.
The electric power only contains the power for the compressor, but not any power for pumps or fans.
Optionally, the model can be configured to represent heat recovery chillers with
a switchover option by setting the parameter have_switchover
to
true
.
In that case an additional Boolean input connector coo
is used.
The chiller is tracking a chilled water supply temperature setpoint at the
outlet of the evaporator barrel if coo
is true
.
Otherwise, if coo
is false
, the chiller is tracking
a hot water supply temperature setpoint at the outlet of the condenser barrel.
See
Buildings.Fluid.Chillers.Examples.ElectricEIR_HeatRecovery
for an example with a chiller operating in heating mode.
This implementation computes the chiller capacity and power consumption the same way as documented in EnergyPlus v22.1.0 Engineering Reference section 14.3.9.2. Especially see equations 14.234 and 14.240 in the referenced document.
The available chiller capacity QEva_flow_ava
is adjusted from
its nominal capacity QEva_flow_nominal
by factor capFunT
as
QEva_flow_ava = QEva_flow_nominal*capFunT
and the compressor power consumption is computed as
P = -QEva_flow_ava*(1/COP_nominal)*EIRFunT*EIRFunPLR*CR.
The models that extend from this base class implement the functions used above in ways that are shown in the table below.
Function | Description | Formulation | |
---|---|---|---|
ElectricEIR |
ElectricReformulatedEIR |
||
capFunT |
Adjusts cooling capacity for current fluid temperatures | Biquadratic on TConEnt and TEvaLvg |
Biquadratic on TConLvg and TEvaLvg |
EIRFunPLR |
Adjusts EIR for the current PLR | Quadratic on PLR | Bicubic on TConLvg and PLR |
EIRFunT |
Adjusts EIR for current fluid temperatures | Biquadratic on TConEnt and TEvaLvg |
Biquadratic on TConLvg and TEvaLvg |
where
TConEnt
is the condenser entering temperature,
TEvaLvg
is the evaporator leaving temperature,
TConLvg
is the condenser leaving temperatore, and
PLR is the part load ratio.
start
values and removed
nominal=1
for performance curves.