.Buildings.Fluid.Chillers.BaseClasses.PartialElectric

Information

Base class for model of an electric chiller, based on the DOE-2.1 chiller model and the CoolTools chiller model that are implemented in EnergyPlus as the models Chiller:Electric:EIR and Chiller:Electric:ReformulatedEIR.

The model takes as an input the set point for the leaving chilled water temperature, which is met if the chiller has sufficient capacity. Thus, the model has a built-in, ideal temperature control. The model has three tests on the part load ratio and the cycling ratio:

  1. The test
      PLR1 =min(QEva_flow_set/QEva_flow_ava, PLRMax)
    
    ensures that the chiller capacity does not exceed the chiller capacity specified by the parameter PLRMax.
  2. The test
      CR = min(PLR1/per.PRLMin, 1.0)
    
    computes a cycling ratio. This ratio expresses the fraction of time that a chiller would run if it were to cycle because its load is smaller than the minimal load at which it can operature. Notice that this model does continuously operature even if the part load ratio is below the minimum part load ratio. Its leaving evaporator and condenser temperature can therefore be considered as an average temperature between the modes where the compressor is off and on.
  3. The test
      PLR2 = max(PLRMinUnl, PLR1)
    
    computes the part load ratio of the compressor. The assumption is that for a part load ratio below PLRMinUnl, the chiller uses hot gas bypass to reduce the capacity, while the compressor power draw does not change.

The electric power only contains the power for the compressor, but not any power for pumps or fans.

Optionally, the model can be configured to represent heat recovery chillers with a switchover option by setting the parameter have_switchover to true. In that case an additional Boolean input connector coo is used. The chiller is tracking a chilled water supply temperature setpoint at the outlet of the evaporator barrel if coo is true. Otherwise, if coo is false, the chiller is tracking a hot water supply temperature setpoint at the outlet of the condenser barrel. See Buildings.Fluid.Chillers.Examples.ElectricEIR_HeatRecovery for an example with a chiller operating in heating mode.

Implementation

This implementation computes the chiller capacity and power consumption the same way as documented in EnergyPlus v22.1.0 Engineering Reference section 14.3.9.2. Especially see equations 14.234 and 14.240 in the referenced document.

The available chiller capacity QEva_flow_ava is adjusted from its nominal capacity QEva_flow_nominal by factor capFunT as

  QEva_flow_ava = QEva_flow_nominal*capFunT

and the compressor power consumption is computed as

  P = -QEva_flow_ava*(1/COP_nominal)*EIRFunT*EIRFunPLR*CR.

The models that extend from this base class implement the functions used above in ways that are shown in the table below.

Function Description Formulation
ElectricEIR ElectricReformulatedEIR
capFunT Adjusts cooling capacity for current fluid temperatures Biquadratic on TConEnt and TEvaLvg Biquadratic on TConLvg and TEvaLvg
EIRFunPLR Adjusts EIR for the current PLR Quadratic on PLR Bicubic on TConLvg and PLR
EIRFunT Adjusts EIR for current fluid temperatures Biquadratic on TConEnt and TEvaLvg Biquadratic on TConLvg and TEvaLvg

where TConEnt is the condenser entering temperature, TEvaLvg is the evaporator leaving temperature, TConLvg is the condenser leaving temperatore, and PLR is the part load ratio.

References

Revisions


Generated at 2024-11-22T19:25:38Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos