.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes,  !- Name
    5651300,                 !- Reference Capacity {W}
    5.50,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.18927,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.18927,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -5651300, COP_nominal = 5.50, PLRMin = 0.19, PLRMinUnl = 0.19, PLRMax = 1.02, mEva_flow_nominal = 1000*0.18927, mCon_flow_nominal = 1000*0.18927, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 29.44, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 15.56, TConEntMax = 273.15 + 29.44, capFunT = {1.299676E+00, 1.790645E-02, -2.522300E-03, 2.536423E-03, -1.128041E-03, 3.003265E-03}, EIRFunT = {7.853207E-01, -1.652255E-02, -3.294526E-04, 4.569179E-03, 1.964013E-04, 1.761497E-04}, EIRFunPLR = {1.629327E-01, 5.709336E-01, 2.659304E-01}, etaMotor = 1.0);

Generated at 2024-04-28T18:16:21Z by OpenModelicaOpenModelica 1.22.3 using GenerateDoc.mos