Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes, !- Name
1258900, !- Reference Capacity {W}
6.26, !- Reference COP {W/W}
8.89, !- Reference Leaving Chilled Water Temperature {C}
26.67, !- Reference Entering Condenser Fluid Temperature {C}
0.02593, !- Reference Chilled Water Flow Rate {m3/s}
0.03823, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.18, !- Minimum Part Load Ratio
1.03, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.18, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
record ElectricEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1258900, COP_nominal = 6.26, PLRMin = 0.18, PLRMinUnl = 0.18, PLRMax = 1.03, mEva_flow_nominal = 1000*0.02593, mCon_flow_nominal = 1000*0.03823, TEvaLvg_nominal = 273.15 + 8.89, TConEnt_nominal = 273.15 + 26.67, TEvaLvgMin = 273.15 + 7.22, TEvaLvgMax = 273.15 + 12.78, TConEntMin = 273.15 + 12.78, TConEntMax = 273.15 + 26.67, capFunT = {1.082071E+00, 3.200888E-02, -3.994780E-03, -5.789604E-03, -8.238938E-04, 2.933539E-03}, EIRFunT = {7.582035E-01, 6.896017E-03, -1.491911E-03, 2.249459E-03, 3.908697E-04, -1.735265E-04}, EIRFunPLR = {2.226232E-01, 5.199282E-01, 2.578470E-01}, etaMotor = 1.0);
Generated at 2024-11-22T19:25:38Z
by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos