.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes,  !- Name
    822900,                  !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04744,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -822900, COP_nominal = 6.28, PLRMin = 0.10, PLRMinUnl = 0.10, PLRMax = 1.03, mEva_flow_nominal = 1000*0.03186, mCon_flow_nominal = 1000*0.04744, TEvaLvg_nominal = 273.15 + 5.56, TConEnt_nominal = 273.15 + 23.89, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 10.00, TConEntMin = 273.15 + 12.78, TConEntMax = 273.15 + 23.89, capFunT = {5.573150E-01, 8.714616E-02, -2.917582E-03, 2.500000E-02, -8.861538E-04, -3.184615E-04}, EIRFunT = {8.029134E-01, 2.171359E-02, 2.388123E-04, -1.096173E-02, 1.065277E-03, -2.057538E-03}, EIRFunPLR = {2.965419E-01, 4.689744E-01, 2.332341E-01}, etaMotor = 1.0);