.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve,  !- Name
    1062000,                 !- Reference Capacity {W}
    5.50,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04573,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05716,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1062000, COP_nominal = 5.50, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.01, mEva_flow_nominal = 1000*0.04573, mCon_flow_nominal = 1000*0.05716, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 29.44, TEvaLvgMin = 273.15 + 6.67, TEvaLvgMax = 273.15 + 10.00, TConEntMin = 273.15 + 21.11, TConEntMax = 273.15 + 29.44, capFunT = {1.025695E+00, 2.327484E-02, -4.693708E-03, -7.092715E-03, -3.754967E-04, 2.843046E-03}, EIRFunT = {2.634070E-01, -7.025220E-03, -4.942613E-04, 2.516931E-02, 1.712769E-04, -4.309735E-04}, EIRFunPLR = {2.576261E-01, 3.416910E-01, 4.007672E-01}, etaMotor = 1.0);