.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes,  !- Name
    3165000,                 !- Reference Capacity {W}
    6.48,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    22.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.09085,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.13627,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -3165000, COP_nominal = 6.48, PLRMin = 0.10, PLRMinUnl = 0.10, PLRMax = 1.03, mEva_flow_nominal = 1000*0.09085, mCon_flow_nominal = 1000*0.13627, TEvaLvg_nominal = 273.15 + 5.56, TConEnt_nominal = 273.15 + 22.78, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 12.78, TConEntMax = 273.15 + 23.89, capFunT = {1.342558E+00, 7.520735E-02, -8.988936E-03, -3.340001E-02, -6.065934E-04, 4.684791E-03}, EIRFunT = {9.347904E-01, 6.551597E-02, -1.242676E-02, -2.799974E-02, 3.323287E-04, 4.803491E-03}, EIRFunPLR = {1.054110E-01, 4.090646E-01, 4.838839E-01}, etaMotor = 1.0);

Generated at 2024-04-28T18:16:21Z by OpenModelicaOpenModelica 1.22.3 using GenerateDoc.mos