.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes,  !- Name
    4019500,                 !- Reference Capacity {W}
    7.35,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07874,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09842,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -4019500, COP_nominal = 7.35, PLRMin = 0.14, PLRMinUnl = 0.14, PLRMax = 1.03, mEva_flow_nominal = 1000*0.07874, mCon_flow_nominal = 1000*0.09842, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 12.78, TEvaLvgMin = 273.15 + 6.67, TEvaLvgMax = 273.15 + 12.22, TConEntMin = 273.15 + 12.78, TConEntMax = 273.15 + 23.89, capFunT = {8.958422E-01, 3.762768E-02, -3.550080E-03, -4.322645E-03, -1.194933E-03, 3.006034E-03}, EIRFunT = {9.322623E-01, -2.157964E-02, -1.435883E-03, 1.379036E-02, -1.491048E-04, 1.302075E-03}, EIRFunPLR = {5.763566E-02, 5.964012E-01, 3.473613E-01}, etaMotor = 1.0);

Generated at 2024-04-28T18:16:21Z by OpenModelicaOpenModelica 1.22.3 using GenerateDoc.mos