.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes,  !- Name
    1519200,                 !- Reference Capacity {W}
    7.10,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03186,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.08139,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1519200, COP_nominal = 7.10, PLRMin = 0.10, PLRMinUnl = 0.10, PLRMax = 1.03, mEva_flow_nominal = 1000*0.03186, mCon_flow_nominal = 1000*0.08139, TEvaLvg_nominal = 273.15 + 8.89, TConEnt_nominal = 273.15 + 26.67, TEvaLvgMin = 273.15 + 7.22, TEvaLvgMax = 273.15 + 12.78, TConEntMin = 273.15 + 12.78, TConEntMax = 273.15 + 26.67, capFunT = {1.265889E+00, 3.401563E-02, -6.532621E-03, -6.600960E-03, -2.172017E-03, 7.121766E-03}, EIRFunT = {9.981236E-01, -1.060763E-02, -3.921458E-03, -1.206761E-02, -1.398595E-04, 3.467199E-03}, EIRFunPLR = {1.563837E-01, 4.894381E-01, 3.541551E-01}, etaMotor = 1.0);

Generated at 2024-11-12T19:25:41Z by OpenModelicaOpenModelica 1.24.0 using GenerateDoc.mos