.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Multistack_MS_172kW_3_67COP_None

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None,  !- Name
    172300,                  !- Reference Capacity {W}
    3.67,                    !- Reference COP {W/W}
    4.44,                    !- Reference Leaving Chilled Water Temperature {C}
    18.33,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.00738,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.00959,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Multistack_MS_172kW_3_67COP_None = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -172300, COP_nominal = 3.67, PLRMin = 0.40, PLRMinUnl = 0.40, PLRMax = 1.03, mEva_flow_nominal = 1000*0.00738, mCon_flow_nominal = 1000*0.00959, TEvaLvg_nominal = 273.15 + 4.44, TConEnt_nominal = 273.15 + 18.33, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 18.33, TConEntMax = 273.15 + 35.00, capFunT = {9.839419E-01, 1.094957E-01, -4.547595E-03, -2.311886E-02, 2.595943E-04, -5.093307E-04}, EIRFunT = {9.396181E-01, -5.754225E-02, 2.561677E-03, 1.081450E-02, 1.839935E-04, 5.269319E-05}, EIRFunPLR = {4.747786E-03, 1.072374E+00, -7.758317E-02}, etaMotor = 1.0);

Generated at 2024-11-12T19:25:41Z by OpenModelicaOpenModelica 1.24.0 using GenerateDoc.mos