.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes,  !- Name
    1125300,                 !- Reference Capacity {W}
    4.89,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02776,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.02618,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1125300, COP_nominal = 4.89, PLRMin = 0.10, PLRMinUnl = 0.10, PLRMax = 1.01, mEva_flow_nominal = 1000*0.02776, mCon_flow_nominal = 1000*0.02618, TEvaLvg_nominal = 273.15 + 5.56, TConEnt_nominal = 273.15 + 23.89, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 10.00, TConEntMin = 273.15 + 15.56, TConEntMax = 273.15 + 23.89, capFunT = {6.151549E-01, -1.181250E-02, -1.491630E-03, 3.326625E-02, -9.315000E-04, 1.771875E-03}, EIRFunT = {5.810580E-01, -4.344257E-02, -5.369108E-04, 2.844405E-02, -1.609390E-04, 7.004346E-04}, EIRFunPLR = {1.807198E-01, -1.469686E-01, 9.658417E-01}, etaMotor = 1.0);