.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1758300, COP_nominal = 5.96, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.03, mEva_flow_nominal = 1000*0.07571, mCon_flow_nominal = 1000*0.09464, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 29.44, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 23.89, TConEntMax = 273.15 + 35.00, capFunT = {9.566057E-02, -2.457943E-02, -6.827143E-03, 7.119360E-02, -2.047680E-03, 5.248800E-03}, EIRFunT = {1.243313E+00, -3.031784E-02, 3.452464E-03, -2.739941E-02, 9.141695E-04, -1.000080E-03}, EIRFunPLR = {1.871377E-01, 5.849639E-01, 2.291447E-01}, etaMotor = 1.0);