.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes,  !- Name
    1680900,                 !- Reference Capacity {W}
    6.59,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04366,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05142,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1680900, COP_nominal = 6.59, PLRMin = 0.10, PLRMinUnl = 0.10, PLRMax = 1.02, mEva_flow_nominal = 1000*0.04366, mCon_flow_nominal = 1000*0.05142, TEvaLvg_nominal = 273.15 + 5.56, TConEnt_nominal = 273.15 + 23.89, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 10.00, TConEntMin = 273.15 + 18.33, TConEntMax = 273.15 + 23.89, capFunT = {6.792987E-01, -5.291217E-02, -5.280108E-03, 5.252682E-02, -2.523689E-03, 7.344940E-03}, EIRFunT = {4.344630E-01, -5.781149E-03, 2.852311E-04, 2.723246E-02, 1.280801E-04, -8.964328E-04}, EIRFunPLR = {1.619116E-01, 2.362420E-01, 6.032459E-01}, etaMotor = 1.0);