.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve,  !- Name
    1051400,                 !- Reference Capacity {W}
    5.05,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04527,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05659,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1051400, COP_nominal = 5.05, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.01, mEva_flow_nominal = 1000*0.04527, mCon_flow_nominal = 1000*0.05659, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 29.44, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 23.89, TConEntMax = 273.15 + 35.00, capFunT = {9.482157E-01, 3.306737E-02, -6.450072E-05, -3.756522E-03, -6.501672E-05, 2.517986E-15}, EIRFunT = {4.904181E-01, -5.530317E-03, 1.209907E-03, 9.122333E-03, 5.923591E-04, -1.469958E-03}, EIRFunPLR = {2.590465E-01, 2.148987E-01, 5.265039E-01}, etaMotor = 1.0);

Generated at 2024-04-28T18:16:21Z by OpenModelicaOpenModelica 1.22.3 using GenerateDoc.mos