Performance data for chiller model.
This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve, !- Name
1051400, !- Reference Capacity {W}
5.05, !- Reference COP {W/W}
6.67, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.04527, !- Reference Chilled Water Flow Rate {m3/s}
0.05659, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.20, !- Minimum Part Load Ratio
1.01, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.20, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
record ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -1051400, COP_nominal = 5.05, PLRMin = 0.20, PLRMinUnl = 0.20, PLRMax = 1.01, mEva_flow_nominal = 1000*0.04527, mCon_flow_nominal = 1000*0.05659, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 29.44, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 23.89, TConEntMax = 273.15 + 35.00, capFunT = {9.482157E-01, 3.306737E-02, -6.450072E-05, -3.756522E-03, -6.501672E-05, 2.517986E-15}, EIRFunT = {4.904181E-01, -5.530317E-03, 1.209907E-03, 9.122333E-03, 5.923591E-04, -1.469958E-03}, EIRFunPLR = {2.590465E-01, 2.148987E-01, 5.265039E-01}, etaMotor = 1.0);
Generated at 2024-11-12T19:25:41Z
by OpenModelicaOpenModelica 1.24.0 using GenerateDoc.mos