.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_Valve

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve,  !- Name
    706800,                  !- Reference Capacity {W}
    7.77,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    15.56,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.04921,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03268,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.28,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.28,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_Valve = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -706800, COP_nominal = 7.77, PLRMin = 0.28, PLRMinUnl = 0.28, PLRMax = 1.01, mEva_flow_nominal = 1000*0.04921, mCon_flow_nominal = 1000*0.03268, TEvaLvg_nominal = 273.15 + 5.56, TConEnt_nominal = 273.15 + 15.56, TEvaLvgMin = 273.15 + 5.56, TEvaLvgMax = 273.15 + 11.11, TConEntMin = 273.15 + 15.56, TConEntMax = 273.15 + 23.89, capFunT = {9.362925E-01, 2.940722E-02, 5.726999E-04, -5.696483E-03, -5.569609E-05, -1.708132E-04}, EIRFunT = {6.497944E-01, 6.883157E-03, -5.277681E-04, 1.725788E-02, 6.779317E-04, -1.244055E-03}, EIRFunPLR = {1.997099E-01, 6.754676E-01, 1.243767E-01}, etaMotor = 1.0);

Generated at 2024-04-28T18:16:21Z by OpenModelicaOpenModelica 1.22.3 using GenerateDoc.mos