.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YCAL0033EE_101kW_3_1COP_AirCooled

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP,  !- Name
    100582,                  !- Reference Capacity {W}
    3.1,                     !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    35,                      !- Reference Entering Condenser Fluid Temperature {C}
    0.0043,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.0011,                  !- Reference Condenser Fluid Flow Rate {m3/s}
    ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.15,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    AirCooled,               !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Fraction of Compressor Electric Consumption Rejected by Condenser
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Note that the reference condenser fluid volumetric flow rate listed in the EnergyPlus performance data is not reasonable. The value obtained from the manufacturer data sheet is used instead. The data sheet is available here . Please see the Section for Physical Data and Nominal Ratings and row for Condender Fans Total Chiller CFM.

Definition

record ElectricEIRChiller_York_YCAL0033EE_101kW_3_1COP_AirCooled = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -100582, COP_nominal = 3.1, PLRMin = 0.10, PLRMinUnl = 0.10, PLRMax = 1.15, mEva_flow_nominal = 1000*0.0043, mCon_flow_nominal = 1.2*9.4389, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 35, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 10.0, TConEntMin = 273.15 + 23.89, TConEntMax = 273.15 + 51.67, capFunT = {-0.2660645697, 0.0998714035, -0.0023814154, 0.0628316481, -0.0009644649, -0.0011249224}, EIRFunT = {0.1807017787, 0.0271530312, -0.0004553574, 0.0188175079, 0.0002623276, -0.0012881189}, EIRFunPLR = {0.0, 1.0, 0.0}, etaMotor = 1.0);