recordElectricEIRChiller_York_YK_2201kW_6_69COP_Vanes

ElectricEIRChiller York YK 2201kW/6.69COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes,  !- Name
    2201400,                 !- Reference Capacity {W}
    6.69,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-2201400
COP_nominal6.69
PLRMin0.14
PLRMinUnl0.14
PLRMax1.05
mEva_flow_nominal1000*0.07571
mCon_flow_nominal1000*0.11356
TEvaLvg_nominal273.15 + 6.67
TConEnt_nominal273.15 + 26.11
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConEntMin273.15 + 15.56
TConEntMax273.15 + 29.44
capFunT{5.474968E-01, -4.800356E-03, -6.845886E-03, 6.302552E-02, -2.911528E-03, 6.598690E-03}
EIRFunT{8.234137E-01, 1.308264E-02, -1.147806E-03, -4.071161E-03, 5.220869E-04, -6.312495E-04}
EIRFunPLR{2.653493E-01, 1.444620E-01, 5.911158E-01}
etaMotor1.0