.Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2275kW_6_32COP_Vanes

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes,  !- Name
    2275200,                 !- Reference Capacity {W}
    6.32,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.13,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.13,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Definition

record ElectricEIRChiller_York_YK_2275kW_6_32COP_Vanes = Buildings.Fluid.Chillers.Data.ElectricEIR.Generic(QEva_flow_nominal = -2275200, COP_nominal = 6.32, PLRMin = 0.13, PLRMinUnl = 0.13, PLRMax = 1.03, mEva_flow_nominal = 1000*0.07571, mCon_flow_nominal = 1000*0.11356, TEvaLvg_nominal = 273.15 + 6.67, TConEnt_nominal = 273.15 + 26.11, TEvaLvgMin = 273.15 + 4.44, TEvaLvgMax = 273.15 + 8.89, TConEntMin = 273.15 + 12.78, TConEntMax = 273.15 + 29.44, capFunT = {1.034673E+00, -1.091064E-02, 9.019479E-04, 9.686229E-03, -9.160783E-04, 2.045641E-03}, EIRFunT = {8.326094E-01, -6.056615E-03, -3.016626E-04, -2.498578E-03, 4.933363E-04, -3.125632E-04}, EIRFunPLR = {2.735485E-01, 2.163041E-01, 5.099054E-01}, etaMotor = 1.0);

Generated at 2024-11-12T19:25:41Z by OpenModelicaOpenModelica 1.24.0 using GenerateDoc.mos