Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, Carrier Centurion 50PG24, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 73810.8, !- Rated Total Cooling Capacity {W} 0.71, !- Rated Sensible Heat Ratio 3.95, !- Rated COP 3.776, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name Carrier Centurion 50PG24 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name Carrier Centurion 50PG24 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name Carrier Centurion 50PG24 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name Carrier Centurion 50PG24 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name Carrier Centurion 50PG24 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record Carrier_Centurion_50PG24 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -73810.8, COP_nominal = 3.95, SHR_nominal = 0.71, m_flow_nominal = 1.2*3.776), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {0.5781158, 0.0405917, 0.0000113, -0.0095022, 0.0000001, -0.0000573}, capFunFF = {0.8328798, 0.2403628, -0.0725624}, EIRFunT = {0.5909553, -0.0496529, 0.0016569, 0.0397786, 0.0003938, -0.0016575}, EIRFunFF = {1.0440554, -0.0701720, 0.0258826}, TConInMin = 273.15 + 15.56, TConInMax = 273.15 + 51.67, TEvaInMin = 273.15 + 12.22, TEvaInMax = 273.15 + 26.67, ffMin = 0.75, ffMax = 1.25))});