Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, Carrier Comfort 50ES060, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 17500.95, !- Rated Total Cooling Capacity {W} 0.78, !- Rated Sensible Heat Ratio 3.9, !- Rated COP 0.944, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name Carrier Comfort 50ES060 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name Carrier Comfort 50ES060 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name Carrier Comfort 50ES060 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name Carrier Comfort 50ES060 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name Carrier Comfort 50ES060 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record Carrier_Comfort_50ES060 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -17500.95, COP_nominal = 3.9, SHR_nominal = 0.78, m_flow_nominal = 1.2*0.944), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {1.6380187, -0.0747347, 0.0029747, 0.0015201, -0.0000519, -0.0004509}, capFunFF = {0.8185792, 0.2831771, -0.1017563}, EIRFunT = {-0.2209648, 0.1033303, -0.0030061, -0.0070657, 0.0006322, -0.0002496}, EIRFunFF = {1.0380778, -0.2013868, 0.1633090}, TConInMin = 273.15 + 23.89, TConInMax = 273.15 + 51.67, TEvaInMin = 273.15 + 13.89, TEvaInMax = 273.15 + 22.22, ffMin = 0.875, ffMax = 1.125))});