Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, Carrier Weathermaster 50HJ006, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 18687, !- Rated Total Cooling Capacity {W} 0.73, !- Rated Sensible Heat Ratio 3.9, !- Rated COP 0.944, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name Carrier Weathermaster 50HJ006 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name Carrier Weathermaster 50HJ006 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name Carrier Weathermaster 50HJ006 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name Carrier Weathermaster 50HJ006 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name Carrier Weathermaster 50HJ006 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record Carrier_Weathermaster_50HJ006 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -18687, COP_nominal = 3.9, SHR_nominal = 0.73, m_flow_nominal = 1.2*0.944), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {0.3116765, 0.0622847, -0.0008633, -0.0066556, -0.0000462, 0.0001349}, capFunFF = {0.6583072, 0.5294956, -0.1869478}, EIRFunT = {1.0505234, -0.0653230, 0.0021068, 0.0235557, 0.0004542, -0.0014092}, EIRFunFF = {1.3293472, -0.5218591, 0.1918220}, TConInMin = 273.15 + 23.89, TConInMax = 273.15 + 51.67, TEvaInMin = 273.15 + 16.67, TEvaInMax = 273.15 + 22.22, ffMin = 0.75, ffMax = 1.25))});