Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, Carrier Weathermaster 50HJ012, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 36846.82, !- Rated Total Cooling Capacity {W} 0.73, !- Rated Sensible Heat Ratio 3.71, !- Rated COP 1.888, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name Carrier Weathermaster 50HJ012 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name Carrier Weathermaster 50HJ012 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name Carrier Weathermaster 50HJ012 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name Carrier Weathermaster 50HJ012 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name Carrier Weathermaster 50HJ012 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record Carrier_Weathermaster_50HJ012 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -36846.82, COP_nominal = 3.71, SHR_nominal = 0.73, m_flow_nominal = 1.2*1.888), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {0.5878544, 0.0247382, 0.0001631, -0.0034960, -0.0000889, 0.0001450}, capFunFF = {0.7232943, 0.4292712, -0.1525863}, EIRFunT = {0.6445678, -0.0198276, 0.0010284, 0.0222812, 0.0004996, -0.0015296}, EIRFunFF = {1.2158796, -0.3411366, 0.1251095}, TConInMin = 273.15 + 23.89, TConInMax = 273.15 + 51.67, TEvaInMin = 273.15 + 16.67, TEvaInMax = 273.15 + 22.22, ffMin = 0.75, ffMax = 1.25))});