Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, Goodman CPC060, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 17427.55, !- Rated Total Cooling Capacity {W} 0.72, !- Rated Sensible Heat Ratio 3.95, !- Rated COP 0.944, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name Goodman CPC060 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name Goodman CPC060 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name Goodman CPC060 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name Goodman CPC060 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name Goodman CPC060 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record Goodman_CPC060 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -17427.55, COP_nominal = 3.95, SHR_nominal = 0.72, m_flow_nominal = 1.2*0.944), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {1.3045870, -0.0618386, 0.0024674, 0.0081572, -0.0001826, -0.0001610}, capFunFF = {-0.9361345, 3.4420168, -1.5058824}, EIRFunT = {0.1618862, 0.0531671, -0.0015621, 0.0077612, 0.0001864, -0.0001388}, EIRFunFF = {2.2905751, -2.2915498, 1.0009747}, TConInMin = 273.15 + 18.33, TConInMax = 273.15 + 46.11, TEvaInMin = 273.15 + 15, TEvaInMax = 273.15 + 21.67, ffMin = 0.875, ffMax = 1.125))});