Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, York Affinity DNP060, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 17200, !- Rated Total Cooling Capacity {W} 0.71, !- Rated Sensible Heat Ratio 3.88, !- Rated COP 0.8496, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name York Affinity DNP060 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name York Affinity DNP060 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name York Affinity DNP060 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name York Affinity DNP060 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name York Affinity DNP060 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record York_Affinity_DNP060 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -17200, COP_nominal = 3.88, SHR_nominal = 0.71, m_flow_nominal = 1.2*0.8496), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {0.9829911, -0.0197231, 0.0016341, 0.0058106, -0.0000309, -0.0005776}, capFunFF = {0.9268752, 0.0902018, -0.0175149}, EIRFunT = {0.2246908, 0.0390385, -0.0010832, 0.0080036, 0.0003449, -0.0004327}, EIRFunFF = {2.0004106, -2.4070885, 1.3922562}, TConInMin = 273.15 + 23.89, TConInMax = 273.15 + 51.67, TEvaInMin = 273.15 + 13.89, TEvaInMax = 273.15 + 25, ffMin = 0.833, ffMax = 1.167))});