Performance data for DX single speed air source cooling coil model. This data corresponds to the following EnergyPlus model:
Coil:Cooling:DX:SingleSpeed, York Sunline DR060, !- Name CoolingCoilAvailSched, !- Availability Schedule Name 17398.26, !- Rated Total Cooling Capacity {W} 0.69, !- Rated Sensible Heat Ratio 4.05, !- Rated COP 0.944, !- Rated Air Flow Rate {m3/s} , !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} DXCoilAirInletNode, !- Air Inlet Node Name DXCoilAirOutletNode, !- Air Outlet Node Name York Sunline DR060 CapFT, !- Total Cooling Capacity Function of Temperature Curve Name York Sunline DR060 CapFFF, !- Total Cooling Capacity Function of Flow Fraction Curve Name York Sunline DR060 EIRFT, !- Energy Input Ratio Function of Temperature Curve Name York Sunline DR060 EIRFFF, !- Energy Input Ratio Function of Flow Fraction Curve Name York Sunline DR060 PLFFPLR; !- Part Load Fraction Correlation Curve Name
record York_Sunline_DR060 = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.SingleSpeed.Generic(sta = {Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.Stage(spe = 1800, nomVal = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.NominalValues(Q_flow_nominal = -17398.26, COP_nominal = 4.05, SHR_nominal = 0.69, m_flow_nominal = 1.2*0.944), perCur = Buildings.Fluid.DXSystems.Cooling.AirSource.Data.Generic.BaseClasses.PerformanceCurve(capFunT = {1.4767927, -0.0614116, 0.0027182, -0.0010838, -0.0000353, -0.0003531}, capFunFF = {0.9156325, 0.0076960, 0.0769601}, EIRFunT = {-0.2918107, 0.0950527, -0.0026508, 0.0070978, 0.0005090, -0.0006143}, EIRFunFF = {0.9336732, 0.2228647, -0.1628839}, TConInMin = 273.15 + 23.89, TConInMax = 273.15 + 51.67, TEvaInMin = 273.15 + 13.89, TEvaInMax = 273.15 + 22.22, ffMin = 0.75, ffMax = 1.25))});