.Buildings.Fluid.DXSystems.Cooling.AirSource.Validation.SingleSpeed

Information

This model validates the model Buildings.Fluid.DXSystems.Cooling.AirSource.SingleSpeed.

The difference in results of TOut and XOut at the beginning and end of the simulation is because the mass flow rate is zero. For zero mass flow rate, EnergyPlus assumes steady state condition, whereas the Modelica model is a dynamic model and hence the properties at the outlet are equal to the state variables of the model.

The EnergyPlus results were generated using the example file DXCoilSystemAuto.idf from EnergyPlus 7.1, with a nominal cooling capacity of 10500 Watts instead of using autosizing. This allowed to have a part load ratio of one.

Note that EnergyPlus mass fractions (X) are in mass of water vapor per mass of dry air, whereas Modelica uses the total mass as a reference. Hence, the EnergyPlus values are corrected by dividing them by 1+X.