This record declares the performance data for the air source DX heating coil model. The performance data are structured as follows:
It consists of the following fields:
nSta - Number of stages. Set to 1 for single speed coil,
2 for dual-speed (or dual stage coils), etc.
minSpeRat - Minimum speed ratio, used only for variable speed coils.
sta - Array of records with one performance curve for each stage,
as described below.
Each element of the array per has the following data.
spe - Rotational speed for the respective stage.
(This is only used for variable speed coils to interpolate for
intermediate speeds).
nomVal - Nominal performance values for the respective stage. Data of the
nomVal record are:
Q_flow_nominal - Total rate of heat transfer at nominal conditions.
COP_nominal - Coefficient of performance at nominal conditions.
m_flow_nominal - Evaporator air mass flow rate at nominal conditions.
TEvaIn_nominal - Evaporator air inlet wet-bulb temperature at nominal conditions.
TConIn_nominal - Condenser air inlet temperature at nominal conditions
(for evaporative coils, use wet bulb, otherwise use dry bulb
temperature).
phiIn_nominal - Relative humidity at evaporator inlet at nominal conditions.
p_nominal - Atmospheric pressure at nominal conditions.
per - Array of records with one performance curve for the respective
stage of the coil. That is, the performance curves will be used
in conjunction with the nominal values defined in the record spe:
capFunT - Coefficients of biquadratic polynomial for heating capacity
as a function of temperature.
capFunFF - Polynomial coefficients for heating capacity as a function of
the mass flow fraction.
EIRFunT - Coefficients of biquadratic polynomial for EIR as a function
of temperature.
EIRFunFF - Polynomial coefficients for EIR as a function of the mass flow
fraction.
[TConInMin, TConInMax] - Minimum and maximum condenser air inlet temperatures
for which the performance curves are valid.
Outside this range, they will be linearly extrapolated.
[TEvaInMin, TEvaInMax] - Minimum and maximum evaporator air inlet temperatures
for which the performance curves are valid.
Outside this range, they will be linearly extrapolated.
[ffMin, ffMax] - Minimum and maximum air mass flow fraction (relative to m_flow_nominal)
for which the performance curves are valid.
Outside this range, they will be linearly extrapolated.
There can be an arbitrary number of polynomial coefficients for the record
capFunFF and EIRFunFF.
However, if a coil has multiple stages, then each stage must declare the
same amount of polynomial coefficients. For example, if a
quadratic function is used for stage one, then stage two must also use
a quadratic function.
It also contains settings and performance curves for defrost operation and overall performance modifiers:
defEIRFunT - Coefficients of biquadratic polynomial for EIR for defrost as a
function of temperature.
PLFraFunPLR - Coefficients of polynomial for part-load fraction as a function
of part-load ratio.
defOpe - Defrost operation type.
QDefResCap - Capacity of heating element on outdoor coil (used for resistive defrost).
QCraCap - Capacity of crankcase heater.
defTri - Defrost time fraction calculation method.
tDefRun - Fraction of time for which defrost is run if timed fraction calculation is used.
TDefLim - Maximum temperature at which the defrost operation may be run.