recordGeneric

Generic data record for air cooled rack

Extends from Buildings.Fluid.DataCenters.Racks.BaseClasses.Data.Generic (Generic data record for IT rack).

Information

Generic data record for air-cooled IT rack.

The fan power consumption at full IT utilization is by default set to 4% of the IT load. This setting can be changed through the parameter PFan_nominal.

The parameter fanRelPow describes the normalized fan power consumption based on the normalized fan volume flow rate. By default, this is set to a cubic curve.

The parameters TAirIn_nominal and TAirOut_nominal are used, together with PFan_nominal, to size the fan. The outlet temperature is also used as the set point for the air temperature raise across the rack, if this control option is selected for the rack.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.TemperatureTIn_nominal303.15Rack design inlet air temperature
Modelica.Units.SI.TemperatureTOut_nominal313.15Rack design outlet air temperature
Modelica.Units.SI.SpecificHeatCapacitycpAir_nominalBuildings.Utilities.Psychrometrics.Constants.cpAirSpecific heat capacity of air
Nominal condition
Modelica.Units.SI.HeatFlowRatePIT_nominal (from Generic)IT power consumption at u=1, also called Thermal Design Power (TDP)
Modelica.Units.SI.MassFlowRatem_flow_nominal (from Generic)Nominal mass flow rate
Fan
Modelica.Units.SI.PowerPFan_nominal0.04*PIT_nominalFan power at full IT load PIT_nominal
Realeta_nominal0.7Fan and motor combined efficiency at nominal conditions

Revisions

  • June 26, 2026, by Michael Wetter:
    First implementation.