modelPartialExample

Partial example model for a rear door heat exchanger

Extends from Modelica.Icons.Example (Icon for runnable examples).

Information

Partial example model for a rear door heat exchanger. This model declares the medium packages, nominal parameters, fluid boundary conditions, temperature sensors, and their connections. Extending models must declare the heat exchanger instance hex, provide the value of mAir_flow_nominal, and add the four connections involving hex.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.HeatFlowRateQ_flow_nominal-10000Nominal cooling duty (negative = heat removed from air)
Modelica.Units.SI.TemperatureTAirIn_nominal273.15 + 40Nominal air inlet temperature (warm server exhaust)
Modelica.Units.SI.TemperatureTAirOut_nominal273.15 + 30Nominal air outlet temperature of rear door heat exchanger
Modelica.Units.SI.TemperatureTCooIn_nominal273.15 + 20Nominal coolant inlet temperature
Modelica.Units.SI.TemperatureTCooOut_nominal273.15 + 30Nominal coolant outlet temperature
Modelica.Units.SI.MassFlowRatemAir_flow_nominalQ_flow_nominal/(TAirOut_nominal - TAirIn_nominal)/cpAir_defaultNominal air mass flow rate
Modelica.Units.SI.MassFlowRatemCoo_flow_nominal-Q_flow_nominal/(TCooOut_nominal - TCooIn_nominal)/cpCoo_defaultNominal coolant mass flow rate
Modelica.Units.SI.SpecificHeatCapacitycpAir_defaultMediumAir.specificHeatCapacityCp(MediumAir.setState_pTX(T = MediumAir.T_default, p = MediumAir.p_default, X = MediumAir.X_default[1:MediumAir.nXi]))Specific heat capacity of air
Modelica.Units.SI.SpecificHeatCapacitycpCoo_defaultMediumCoo.specificHeatCapacityCp(MediumCoo.setState_pTX(T = MediumCoo.T_default, p = MediumCoo.p_default, X = MediumCoo.X_default[1:MediumCoo.nXi]))Specific heat capacity of the coolant fluid

Components

TypeNameDefaultDescription
Buildings.Fluid.Sources.Boundary_pTairSinAir pressure reference
Buildings.Fluid.Sources.MassFlowSource_TcooSouCoolant source at nominal conditions
Buildings.Fluid.Sources.Boundary_pTcooSinCoolant pressure reference
Buildings.Fluid.Sensors.TemperatureTwoPortsenTAirInAir inlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTAirOutAir outlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTCooInCoolant inlet temperature sensor
Buildings.Fluid.Sensors.TemperatureTwoPortsenTCooOutCoolant outlet temperature sensor

Contents

NameDescription
MediumCooCoolant medium
MediumAirAir medium

Revisions

  • September 20, 2026, by Michael Wetter:
    First implementation.