modelPartialExample
Partial example model for a rear door heat exchanger
Extends from Modelica.Icons.Example (Icon for runnable examples).
Information
Partial example model for a rear door heat exchanger.
This model declares the medium packages, nominal parameters,
fluid boundary conditions, temperature sensors, and their connections.
Extending models must declare the heat exchanger instance hex,
provide the value of mAir_flow_nominal,
and add the four connections involving hex.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Modelica.Units.SI.HeatFlowRate | Q_flow_nominal | -10000 | Nominal cooling duty (negative = heat removed from air) |
| Modelica.Units.SI.Temperature | TAirIn_nominal | 273.15 + 40 | Nominal air inlet temperature (warm server exhaust) |
| Modelica.Units.SI.Temperature | TAirOut_nominal | 273.15 + 30 | Nominal air outlet temperature of rear door heat exchanger |
| Modelica.Units.SI.Temperature | TCooIn_nominal | 273.15 + 20 | Nominal coolant inlet temperature |
| Modelica.Units.SI.Temperature | TCooOut_nominal | 273.15 + 30 | Nominal coolant outlet temperature |
| Modelica.Units.SI.MassFlowRate | mAir_flow_nominal | Q_flow_nominal/(TAirOut_nominal - TAirIn_nominal)/cpAir_default | Nominal air mass flow rate |
| Modelica.Units.SI.MassFlowRate | mCoo_flow_nominal | -Q_flow_nominal/(TCooOut_nominal - TCooIn_nominal)/cpCoo_default | Nominal coolant mass flow rate |
| Modelica.Units.SI.SpecificHeatCapacity | cpAir_default | MediumAir.specificHeatCapacityCp(MediumAir.setState_pTX(T = MediumAir.T_default, p = MediumAir.p_default, X = MediumAir.X_default[1:MediumAir.nXi])) | Specific heat capacity of air |
| Modelica.Units.SI.SpecificHeatCapacity | cpCoo_default | MediumCoo.specificHeatCapacityCp(MediumCoo.setState_pTX(T = MediumCoo.T_default, p = MediumCoo.p_default, X = MediumCoo.X_default[1:MediumCoo.nXi])) | Specific heat capacity of the coolant fluid |
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Fluid.Sources.Boundary_pT | airSin | Air pressure reference | |
| Buildings.Fluid.Sources.MassFlowSource_T | cooSou | Coolant source at nominal conditions | |
| Buildings.Fluid.Sources.Boundary_pT | cooSin | Coolant pressure reference | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTAirIn | Air inlet temperature sensor | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTAirOut | Air outlet temperature sensor | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTCooIn | Coolant inlet temperature sensor | |
| Buildings.Fluid.Sensors.TemperatureTwoPort | senTCooOut | Coolant outlet temperature sensor |
Contents
| Name | Description |
|---|---|
| Coolant medium | |
| Air medium |
Revisions
-
September 20, 2026, by Michael Wetter:
First implementation.