Component that calculates the heat losses at the end of a plug flow pipe when the flow goes in the design direction.
The governing equations are
Tout = Tb + (Tin - Tb) exp((tout - tin)/tauchar)
with
tauchar = R C
This model is based on the following assumptions:
Heat losses are only considered in design flow direction. For
heat loss consideration in both directions, use one of these models
at both ends of a Buildings.Fluid.FixedResistances.BaseClasses.PlugFlow
model. The outlet temperature is calculated as in the equation
above, using the inlet temperature at port_a and the
instantaneous time delay and boundary temperature. The boundary
temperature can be either the air temperature or the undisturbed
ground temperature, depending on the definition of the thermal
resistance R.
This component requires the delay time and the instantaneous ambient temperature as an input. This component is to be used in single pipes or in more advanced configurations where no influence from other pipes is considered.