.Buildings.Fluid.Geothermal.ZonedBorefields.BaseClasses.PartialStorage

Partial model for borehole thermal energy storage with independent borefield zones

Information

This model simulates a borehole thermal energy storage system with multiple zones of boreholes. Boreholes within the same zone are connected in parallel. The borefield configuration and thermal parameters are defined in the borFieDat record.

Heat transfer to the soil is modeled using one borehole heat exchanger (To be added in an extended model) per borefield zone. The fluid mass flow rate into each borehole is divided to reflect the per-borehole fluid mass flow rate. The borehole model calculates the dynamics within the borehole itself using an axial discretization and a resistance-capacitance network for the internal thermal resistances between the individual pipes and between each pipe and the borehole wall.

The ground thermal response at each borehole segment is evaluated using analytical thermal response factors. Spatial and temporal superposition are used to evaluate the total temperature change at each of the borehole segments.

Contents

NameDescription
 MediumMedium in the borehole pipes

Revisions


Generated at 2025-04-15T18:20:12Z by OpenModelicaOpenModelica 1.25.0 using GenerateDoc.mos