.Buildings.Fluid.HeatPumps.Data.EquationFitReversible.EnergyPlus

Information

This data corresponds to the EnergyPlus example file GSHPSimple-GLHE.idf from EnergyPlus 9.1, with a nominal cooling capacity of 39890 Watts and nominal heating capacity of 39040 Watt.

Definition

record EnergyPlus = Buildings.Fluid.HeatPumps.Data.EquationFitReversible.Generic(dpHeaSou_nominal = 30000, dpHeaLoa_nominal = 30000, hea(TRefLoa = 10 + 273.15, TRefSou = 10 + 273.15, Q_flow = 39040.92, P = 5130, mLoa_flow = 1.89, mSou_flow = 1.89, coeQ = {-3.33491153, -0.51451946, 4.51592706, 0.01797107, 0.155797661}, coeP = {-8.93121751, 8.57035762, 1.29660976, -0.21629222, 0.033862378}), coo(TRefSou = 10 + 273.15, TRefLoa = 10 + 273.15, Q_flow = -39890.91, P = 4790, coeQ = {-1.52030596, 3.46625667, -1.32267797, 0.09395678, 0.038975504}, coeP = {-8.59564386, 0.96265085, 8.69489229, 0.02501669, -0.20132665}));

Revisions


Generated at 2024-11-22T19:25:38Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos