Performance data for reverse heat pump model. This data corresponds to the following https://www.trane.com/wshp.pdf catalog data.
Trane EXW 70kW/4.11COP, !- Name 77000, !- Reference Heating Capacity {W} 55680, !- Reference Cooling Capacity {W} 4.10, !- Reference COP {W/W} 13.5, !- Refrence EER{BTUh/W} 0.0018, !- Reference Evaporator Water Flow Rate {m3/s} 0.0018, !- Reference Condenser Water Flow Rate {m3/s}
record Trane_Axiom_EXW240 = Buildings.Fluid.HeatPumps.Data.EquationFitReversible.Generic(dpHeaSou_nominal = 33530, dpHeaLoa_nominal = 32460, hea(TRefLoa = 53 + 273.15, TRefSou = 18 + 273.15, Q_flow = 77000.00, P = 18000, mSou_flow = 1.893, mLoa_flow = 1.893, coeQ = {-4.23, -1.24, 6.28, 0.01, 0.08}, coeP = {-5.55, 5.08, 1.01, -0.04, 0.00}), coo(TRefSou = 28 + 273.15, TRefLoa = 12 + 273.15, Q_flow = -55680.00, P = 14244.44, coeQ = {-5.79235417, 9.83800467, -3.19795605, 0.32498894, 0.043752306918433}, coeP = {-6.37109639, 1.27560526, 5.81780490, 0.03132874, -0.082990443216406}));