This model uses two-dimensional table data typically given by
manufacturers as required by e.g. European Norm 14511 or ASHRAE 205
to calculate QCon_flow and PEle.
For different condenser outlet and evaporator inlet temperatures, the tables must provide two of the three following values: electrical power consumption, evaporator heat flow rate, and COP.
Note that losses are often implicitly included in measured data. In this case, the frosting modules should be disabled.
For the scaling factor, the table data for condenser heat flow
rate (QConTabDat_flow) is evaluated at nominal
conditions. Hence, the scaling factor is
scaFac = QCon_flow_nominal/QConTabDat_flow(TEva_nominal, TCon_nominal).
Using scaFac, the table data is scaled linearly.
This implies a constant COP over different design sizes:
QCon_flow = scaFac * tabQCon_flow.y
PEle = scaFac * tabPel.y
yMea is used to
scale the ouput of the tables linearly. For models including the
compressor speed, check the SDF-Library dependent refrigerant cycle
models in the AixLib Library.EN 14511-2018: Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors https://www.beuth.de/de/norm/din-en-14511-1/298537524