.Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Diversion

Information

Summary

This configuration (see schematic below) is used for constant flow primary circuits and variable flow consumer circuits where the consumer circuit has the same supply temperature set point as the primary circuit.

Schematic

The following table presents the main characteristics of this configuration.

Primary circuit Constant flow
Secondary (consumer) circuit Variable flow
Typical applications Single heating or cooling coil served by a constant flow circuit
Non-recommended applications DHC systems due to the significant recirculating primary flow rate at low load
Heating systems with condensing boilers for the same reason
Built-in valve control options No built-in controls
Control valve selection β = ΔpA-AB / (Δp2 + ΔpA-AB) = ΔpA-AB / (Δp1 - ΔpAB-b1)
The valve is sized with a pressure drop of Δp2 for a mass flow rate equal to the consumer circuit design flow.
Balancing requirement The bypass balancing valve is not needed in most cases. If the valve has a low authority and the consumer circuit has a high pressure drop (compared to the primary pump head) then a bypass balancing valve should be used and sized so that ΔpJ-B + ΔpB-AB = Δp2 + ΔpA-AB for a mass flow rate equal to the consumer circuit design flow.
Lumped flow resistances include
(With the setting use_lumFloRes=true.)
Direct branch: control valve direct branch val.res1 and whole consumer circuit between b2 and a2
Bypass branch: control valve bypass branch val.res3 and bypass balancing valve res3

Additional comments

See the example Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Examples.DiversionOpenLoop for additional comments regarding the need for a balanced bypass.

Revisions


Generated at 2024-11-22T19:25:38Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos