.Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Examples.DecouplingMixing

Information

This model represents a cooling system where the configuration Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Decoupling is used in conjunction with Buildings.Fluid.HydronicConfigurations.PassiveNetworks.SingleMixing. The combined configuration serves as the interface between a variable flow primary circuit and a variable flow consumer circuit. The primary circuit has a constant supply temperature. The consumer circuit has a varying supply temperature set point that is reset based on the terminal valve opening, with the most open valve being kept 90% open.

Note the following settings.

The fact that the load seems unmet at partial load (see plot #4) is due to the load model that does not guarantee a linear variation of the load with the input signal in cooling mode, see Buildings.Fluid.HydronicConfigurations.ActiveNetworks.Examples.BaseClasses.Load.

Revisions


Generated at 2024-11-22T19:25:38Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos