Validation model for multi zone VAV AHU outdoor and return air damper position modulation sequence
This example validates
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.AHUs.MultiZone.VAV.Economizers.Subsequences.Modulation
for a varying supply air temperature control loop signal.
The instance mod
is in normal operation, whereas
for the instance modFre
, the damper limits are
as if the mixed air temperature were below its freezing set point.
-
October 13, 2017, by Michael Wetter:
Added additional instance to validate the behavior when dampers are
such positioned that they prevent the mixed air temperature from being
below the freezing set point.
-
June 30, 2017, by Milica Grahovac:
First implementation.