Block that outputs the zone setpoint temperature (TZonCooSet,
TZonHeaSet) and system operation mode (yOpeMod).
The sequence consists of the following two subsequences.
The subsequence outputs one of seven types of system operation mode (occupied, warm-up,
cooldown, setback, freeze protection setback, setup, unoccupied) according
to current time, the time to next occupied hours tNexOcc and
current zone temperature TZon.
See
Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.Generic.SetPoints.OperationMode.
It sets the zone temperature setpoint according to the globally specified setpoints, the local setpoint adjustments, the demand limits adjustment, the window status and the occupancy status. See Buildings.Obsolete.Controls.OBC.ASHRAE.G36_PR1.TerminalUnits.SetPoints.ZoneTemperatures.
This version is for a single zone only to be used in the Single Zone VAV sequence.