The plant is enabled when it has been disabled for at least the duration dtRun
and:
-
Number of plant requests > number of ignored requests
nReqIgn
, and
-
For cooling systems: outdoor air temperature > outdoor air lockout
temperature
TOutLck
, and
-
For heating systems: outdoor air temperature < outdoor air lockout
temperature
TOutLck
, and
-
The enable schedule is active.
The plant is disabled when it has been enabled for at least the duration
dtRun
and:
-
Number of plant requests ≤ number of ignored requests
nReqIgn
for at least the duration dtReq
, or
-
For cooling systems: outdoor air temperature < outdoor air lockout
temperature
TOutLck
minus hysteresis dTOutLck
, or
-
For heating systems: outdoor air temperature > outdoor air lockout
temperature
TOutLck
plus hysteresis dTOutLck
, or
-
The plant enable schedule is inactive.
-
March 29, 2024, by Antoine Gautier:
First implementation.
Generated at 2024-12-11T19:25:49Z
by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos