Case 900, but cooling based on schedule, night venting, and no
heating
This model is used for the test case 950 of the BESTEST
validation suite. Case950 is the same as Case900, but with the
following modifications:
- From 1800 hours to 0700 hours, vent fan = on
- From 0700 hours to 1800 hours, vent fan = off
- Heating is always off
- From 0700 hours to 1800 hours, cooling is on if zone
temperature > 27°C, otherwise cool = off.
- From 1800 hours to 0700 hours, cooling is always off.
- Ventilation fan capacity is 1700 standard m3/h (in
addition to specified infiltration rate). After adjustment for the
altitude, the capacity is 1409 m3/h.
- No waste heat from fan.
- May 12, 2023, by Jianjun Hu:
Added test acceptance criteria limits. This is for issue
3396.
- May 12, 2022, by Jianjun Hu:
Changed the ventilation fan capacity from 1703.16 m3/h to 1700 m3/h
and consider the adjustment for the altitude, eventually to be 1409
m3/h.
This is for #3005.
- July 16, 2012, by Michael Wetter:
Revised implementation to extend from base case to avoid duplicate
code. Merged model into the Buildings library.
- June 5, 2012, by Sebastian Vock and Rafael Velazquez:
First implementation.