Case 900, but cooling based on schedule, night venting, and no heating
This model is used for the test case 950 of the BESTEST validation suite.
Case950 is the same as Case900, but with the following modifications:
-
From 1800 hours to 0700 hours, vent fan = on
-
From 0700 hours to 1800 hours, vent fan = off
-
Heating is always off
-
From 0700 hours to 1800 hours, cooling is on if zone temperature > 27°C,
otherwise cool = off.
-
From 1800 hours to 0700 hours, cooling is always off.
-
Ventilation fan capacity is 1700 standard m3/h (in addition to specified
infiltration rate). After adjustment for the altitude, the capacity is 1409 m3/h.
-
No waste heat from fan.
-
May 12, 2023, by Jianjun Hu:
Added test acceptance criteria limits.
This is for
issue 3396.
-
May 12, 2022, by Jianjun Hu:
Changed the ventilation fan capacity from 1703.16 m3/h to 1700 m3/h and consider the adjustment
for the altitude, eventually to be 1409 m3/h.
This is for #3005.
-
July 16, 2012, by Michael Wetter:
Revised implementation to extend from base case to avoid duplicate code.
Merged model into the Buildings library.
-
June 5, 2012, by Sebastian Vock and Rafael Velazquez:
First implementation.