This model is used for the test case 950 of the BESTEST
validation suite. Case950 is the same as Case900, but with the
following modifications:
- From 18h00 hours to 07h00 hours, vent fan = on
- From 07h00 hours to 18h00 hours, vent fan = off
- Heating is always off
- From 07h00 hours to 18h00 hours, cooling is on if zone
temperature > 27°C, otherwise cool = off.
- From 18h00 hours to 07h00 hours, cooling is always off.
- Ventilation fan capacity is 1700 standard m3/h (in
addition to specified infiltration rate). After adjustment for the
altitude, the capacity is 1409 m3/h.
- No waste heat from fan.
- Mar 2, 2024, by Alessandro Maccarini:
First implementation.