This model is used for the test case 950 of the BESTEST validation suite.
Case950 is the same as Case900, but with the following modifications:
-
From 18h00 hours to 07h00 hours, vent fan = on
-
From 07h00 hours to 18h00 hours, vent fan = off
-
Heating is always off
-
From 07h00 hours to 18h00 hours, cooling is on if zone temperature > 27°C,
otherwise cool = off.
-
From 18h00 hours to 07h00 hours, cooling is always off.
-
Ventilation fan capacity is 1700 standard m3/h (in addition to specified
infiltration rate). After adjustment for the altitude, the capacity is 1409 m3/h.
-
No waste heat from fan.
-