.Buildings.Utilities.Psychrometrics.Functions.pW_TDewPoi_amb

Information

Dew point temperature calculation for moist air between 0 degC and 30 degC.

The correlation used in this model is valid for dew point temperatures between 0°C and 30°C. It is an approximation to the correlation from 2005 ASHRAE Handbook, p. 6.2, which is valid in a wider range of temperatures and implemented in Buildings.Utilities.Psychrometrics.Functions.pW_TDewPoi. The approximation error of this simplified function is below 5% for a temperature of 0°C to 30°C. The benefit of this simpler function is that it can be inverted analytically, whereas the other function requires a numerical solution.

Interface

function pW_TDewPoi_amb
  extends Modelica.Icons.Function;
  input Modelica.Units.SI.Temperature T "Dew point temperature";
  output Modelica.Units.SI.Pressure p_w(displayUnit = "Pa", min = 100) "Water vapor partial pressure";
end pW_TDewPoi_amb;

Revisions


Generated at 2024-12-11T19:25:49Z by OpenModelicaOpenModelica 1.24.2 using GenerateDoc.mos