modelThreeRoomsContamDiscretizedDoor

Model with three rooms for the validation of the multizone air exchange models

Extends from Buildings.Airflow.Multizone.Validation.ThreeRoomsContam (Model with three rooms for the validation of the multizone air exchange models).

Information

This model is identical to Buildings.Airflow.Multizone.Validation.ThreeRoomsContam except that it uses a different door model.

This model has been used for a comparative model validation between CONTAM and the Buildings library. See Wetter (2006) for details of the validation.

References

Michael Wetter. Multizone Airflow Model in Modelica. Proc. of the 5th International Modelica Conference, p. 431-440. Vienna, Austria, September 2006.

Components

TypeNameDefaultDescription
Buildings.Fluid.MixingVolumes.MixingVolumevolEas (from ThreeRoomsContam)Air volume east room
Buildings.Airflow.Multizone.OrificeoriOutBot (from ThreeRoomsContam)Orifice at bottom of facade
Buildings.Airflow.Multizone.MediumColumncolOutTop (from ThreeRoomsContam)Medium column for bottom floor outside air
Buildings.Airflow.Multizone.OrificeoriOutTop (from ThreeRoomsContam)Orifice at top of facade
Buildings.Airflow.Multizone.MediumColumncolEasInTop (from ThreeRoomsContam)Medium column for bottom floor
Buildings.Fluid.Sources.Boundary_pTvolOut (from ThreeRoomsContam)Outside air boundary condition
Buildings.Airflow.Multizone.MediumColumncolEasInBot (from ThreeRoomsContam)Medium column for bottom floor
Buildings.Airflow.Multizone.MediumColumncolOutBot (from ThreeRoomsContam)Medium column for bottom floor outside air
Buildings.Airflow.Multizone.MediumColumncolWesBot (from ThreeRoomsContam)Medium column for bottom floor
Buildings.Airflow.Multizone.OrificeoriWesTop (from ThreeRoomsContam)Orifice between top and bottom west floor
Buildings.Airflow.Multizone.MediumColumncolWesTop (from ThreeRoomsContam)Medium column for top floor
DoorOpendooOpeClo (from ThreeRoomsContam)
Buildings.Fluid.MixingVolumes.MixingVolumevolWes (from ThreeRoomsContam)Air volume west floor
Buildings.Airflow.Multizone.MediumColumncol1EasBot (from ThreeRoomsContam)Medium column for bottom floor
Buildings.Airflow.Multizone.OrificeoriEasTop (from ThreeRoomsContam)Orifice between top and bottom east floor
Buildings.Airflow.Multizone.MediumColumncolEasTop (from ThreeRoomsContam)Medium column for top floor
Buildings.Fluid.MixingVolumes.MixingVolumevolTop (from ThreeRoomsContam)Air volume top floor
Buildings.HeatTransfer.Sources.FixedTemperatureTTop (from ThreeRoomsContam)Fixed temperature
Buildings.HeatTransfer.Sources.FixedTemperatureTWes (from ThreeRoomsContam)Fixed temperature
Buildings.HeatTransfer.Sources.FixedTemperatureTEas (from ThreeRoomsContam)Fixed temperature
Modelica.Thermal.HeatTransfer.Components.ThermalConductorconTop (from ThreeRoomsContam)Thermal conductor
Modelica.Thermal.HeatTransfer.Components.ThermalConductorconWes (from ThreeRoomsContam)Thermal conductor
Modelica.Thermal.HeatTransfer.Components.ThermalConductorconEas (from ThreeRoomsContam)Thermal conductor
Modelica.Blocks.Sources.Constantopen1Constant signal for door opening

Revisions

  • October 9, 2020, by Michael Wetter:
    Refactored model to use the base class Buildings.Airflow.Multizone.Validation.ThreeRoomsContam.
  • May 15, 2019, by Jianjun Hu:
    Replaced fluid source. This is for #1072.
  • December 22, 2014 by Michael Wetter:
    Removed Modelica.Fluid.System to address issue #311.
  • June 26, 2014, by Michael Wetter:
    Set the initial conditions to be fixed to avoid a translation warning. This required adding a heat conductor between each volume and its prescribed temperature in order to avoid an overdetermined system of equations.
  • November 10, 2011, by Michael Wetter:
    Added documentation.