modelSupplyTemperature
Validate model for calculating supply air temperature of multi zone VAV AHU
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.SupplyTemperature for a change of outdoor temperature, operation mode, supply fan status, maximum supply temperature, to specify the supply air temperature for systems with multiple zones.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.SupplyTemperature | conTSupSet | Supply air temperature setpoint for multi zone system | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin | outTem | Outdoor air temperature | |
| Buildings.Controls.OBC.CDL.Logical.Sources.Pulse | supFanSta | Supply fan status | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | opeMod | Operation mode | |
| Buildings.Controls.OBC.CDL.Reals.Abs | abs | Block generates absolute value of input | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Sin | sine | Block generates sine signal | |
| Buildings.Controls.OBC.CDL.Conversions.RealToInteger | reaToInt1 | Convert real to integer | |
| Buildings.Controls.OBC.CDL.Reals.Round | round1 | Round real number to given digits | |
| Buildings.Controls.OBC.CDL.Conversions.RealToInteger | reaToInt2 | Convert real to integer | |
| Buildings.Controls.OBC.CDL.Reals.Round | round2 | Round real number to given digits |
Revisions
-
July 11, 2017, by Jianjun Hu:
First implementation.