modelModulation_TSup

Validation model for single zone VAV AHU outdoor and return air damper position modulation sequence

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Economizers.Subsequences.Modulation for supply air temeperature TSup and supply air temperature heating setpoint TSupSet control signals.

Parameters

TypeNameDefaultDescription
RealTSupSet291.15Supply air temperature setpoint

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.Economizers.Subsequences.ModulationmodEconomizer modulation sequence
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTSupSetSigSupply air temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.RampTSupMeasured supply air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantoutDamPosMinMinimum outdoor air damper position
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantoutDamPosMaxMaximum outdoor air damper position
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantRetDamPosMinMinimum return air damper position
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantRetDamPosMaxMaximum return air damper position
Buildings.Controls.OBC.CDL.Logical.Sources.ConstantfanStatusFan is on

Revisions

  • July 29, 2019, by Kun Zhang:
    Modified inputs for better representation of results plotting.
  • October 31, 2018, by David Blum:
    Added heating coil output.
  • July 07, 2017, by Milica Grahovac:
    First implementation.