modelSupplyTemperature
Validation model for supply temperature
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.SetPoints.SupplyTemperature for a change in the loop inputs and the effects on the supply temperature setpoints.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.AHUs.SingleZone.VAV.SetPoints.SupplyTemperature | temSet | Block that computes the setpoints for temperature | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | TZonCooSet | Zone cooling set point | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Constant | TZonHeaSet | Zone heating set point | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | uHea | Heating control signal | |
| Buildings.Controls.OBC.CDL.Reals.Sources.Ramp | uCoo | Cooling control signal |
Revisions
-
June 30, 2025, by Jianjun Hu:
First implementation.