modelResetMinBypass
Validate sequence of reseting minimum flow bypass
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Staging.Processes.Subsequences.ResetMinBypass.
The instance minBypRes shows the process of changing the bypass valve
when the minimum bypass chilled water flow setpoint has been changed, when the
plant is in a staging up process.
-
Before 90 seconds, the plant is not in the staging process. There is no change to the
minimum bypass valve (
yMinBypRes=true). -
At 90 seconds, the plant starts staging process. However, it is not yet to change
the bypass valve (
yMinBypRes=true). As the upstream subprocess has not finished (uUpsDevSta=false). -
At 120 seconds, the plant is still in the staging process and the upstream subprocess
has finished (
uUpsDevSta=true). It starts changing the minimum flow setpoint (uSetChaPro=true) and changing the bypass valve (yMinBypRes=false). The measured chiller water flow becomes different from its setpoint. -
At 300 seconds, it finished the setpoint changing process and the
uSetChaProbecomes false. The chilled water flow has been greater than the setpoint. -
After 60 seconds to 360 seconds, the minimum bypass valve position changing process
is finished (
yMinBypRes=true).
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Staging.Processes.Subsequences.ResetMinBypass | minBypRes | Check if the setpoint has achieved |
Revisions
-
September 26, 2019, by Jianjun Hu:
First implementation.