packageValidation

Collection of validation models

Information

This package contains validation models for the classes in Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Staging.Processes.Subsequences.

Note that most validation models contain simple input data which may not be realistic, but for which the correct output can be obtained through an analytic solution. The examples plot various outputs, which have been verified against these solutions. These model outputs are stored as reference data and used for continuous validation whenever models in the library change.

Contents

NameDescription
CHWIsoValValidate isolation valve enable and disable sequence
DisableChillerValidate sequence of disabling chiller during stage-down process
DownStartWithOnValidate sequence of starting the staging down process which requires enabling a chiller
DownStartWithoutOnValidate sequence of starting the staging down process which does not require enabling a chiller
EnableCWPumpValidate sequence of generating stage index for CW pump control
EnableChillerValidate sequence of enabling and disabling chiller
HeadControlValidate sequence of enabling and disabling head pressure control loop
NextChillerValidate sequence of identifying next enable or disable chillers
ReduceDemandValidate sequence of reducing chiller demand when there is stage up command
ResetMinBypassValidate sequence of reseting minimum flow bypass
UpEndWithOffValidate sequence of end staging up process which requires chiller OFF
UpEndWithoutOffValidate sequence of end staging up process which does not require chiller OFF